Output Module (L100C)

Output Module (L100C)
+
  • Output Module (L100C)

Product Consulting

Product Overview

The L100C module outputs a set of normally open contacts and monitors the output wiring and external power supply. The LED indicators on this module can display off, flashing, or steady states through command codes sent by the controller. The relay inside the module operates or resets based on commands from the controller.

The address of this module is written by the address programmer LP100, with an address setting range of 001 to 199.

 

Technical Characteristics

Operating Temperature: -10ºC to 55ºC (14ºF to 131ºF)
Operating Humidity: 5% to 95% RH relative humidity, non-condensing
Rated Operating Voltage: DC24V
Static Current: 380μA @DC24V without communication
Lighting Current: 1.6mA @DC24V (LED on)
Terminal Resistance: 47KQ
External Power Input Voltage: Rated DC24V
External Power Input Current: Maximum 1A
Output Contact Capacity: 1A, DC30V (resistive load)
Dimensions: 85mm long x 85mm wide x 36mm high (including base, see Figure 2A)
Weight: Approximately 100g
Software Version: A
Implementation Standards: GB16806-2006

Key words:

Point-type photoelectric smoke fire detector

Point-type temperature sensing fire detector

Fire alarm with sound and light

Manual fire alarm button

Fire hydrant button

Module

Standalone photoelectric smoke fire detector

Others

Related Products