Product Overview
The L100CM input/output module features a single output and a single input channel. Two independent LED indicators can display off, flashing, or steady states based on command codes from the controller.
The input channel monitors a passive normally open contact and feeds its status back to the controller. The output channel outputs a set of normally open contacts and monitors the output wiring and external input power.
The address of this module is written by the address writer LP100, with an address range of 001 to 199. The written address is the address N of the output channel, and the address N+1 of the input channel is generated automatically. This module is set to dual address at the factory.
Technical Specifications
Operating Temperature: | -10°C to 55°C (14°F to 131°F) |
Operating Humidity: | 5% to 95% RH relative humidity, non-condensing |
Rated Operating Voltage: | DC24V |
Static Current: | 410μA @DC24V without communication |
Lighting Current: | 2.3mA @DC24V (LED on) |
Terminal Resistance: | 47KQ |
External Power Input Voltage: | Rated DC24V |
External Power Input Current: | Maximum 1A |
Output Contact Capacity: | 1A, DC30V (resistive load) |
Dimensions: | 85mm long x 85mm wide x 36mm high (including base, see Figure 2A) |
Weight: | Approximately 110g |
Software Version: | A |
Implementation Standards: | GB16806-2006 |
Key words:
Point-type photoelectric smoke fire detector
Point-type temperature sensing fire detector
Fire alarm with sound and light
Manual fire alarm button
Fire hydrant button
Module
Standalone photoelectric smoke fire detector
Others
Related Products