Isolation Module (L400ISO)

Isolation Module (L400ISO)
+
  • Isolation Module (L400ISO)

Product Consulting

Product Overview

In a bus-based fire automatic alarm system, it is common for a local bus to fail (e.g., short circuit), causing the entire alarm system to become paralyzed. By inserting the L400ISO isolation module into various segments of the bus or at the junction of the main line and branch lines, once a short circuit occurs somewhere in the bus loop, the isolation module will isolate the faulty part of the bus from the entire system, ensuring that other parts of the system can operate normally. Once the faulty part of the bus is repaired, the isolation module can automatically resume operation and reintegrate the isolated part back into the system.

 

Technical Characteristics

Operating Temperature Range:   -10ºC to 55ºC (14ºF to 131ºF)
Operating Humidity Range:   5% to 95% RH relative humidity, no condensation
Rated Operating Voltage:   DC24V
Static Current:   <150uA
Operating Current:   <13mA
Maximum Output Load:   0.5A, DC30V
LED Indicator:   The yellow indicator light flashes during normal operation and stays on during activation.
Dimensions:   86mm long x 86mm wide x 34mm high (including base, see Figure 2A)
Weight:   Approximately 90g (with base)
Software Version:   A

Key words:

Point-type photoelectric smoke fire detector

Point-type temperature sensing fire detector

Fire alarm with sound and light

Manual fire alarm button

Fire hydrant button

Module

Standalone photoelectric smoke fire detector

Others

Related Products


Product Consulting


If you have any questions, you can leave us a message. We have professionals to reply to you. Please fill in the correct contact information!

Submit Message
%{tishi_zhanwei}%
%{tishi_zhanwei}%