Product Overview
The L300CM input/output module features a single output and a single input channel. Two independent LED indicators can display off, flashing, or steady states based on command codes from the controller.
The input channel monitors a passive normally open contact and feeds its status back to the controller. The output channel outputs a set of normally open contacts and monitors the output wiring and external input power.
The address of this module is written by the address programmer LP100, with an address range of 001 to 199. The written address is the address N of the output channel, and the address N+1 of the input channel is generated automatically. This module is set to dual address at the factory.
Technical Specifications
Operating Temperature Range: | -10°C to 55°C (14°F to 131°F) |
Operating Humidity Range: | 5% to 95% R.H. relative humidity, non-condensing |
Rated Power Supply Voltage: | DC24V |
Static Current: | 410HA @DC24V without communication |
Lighting Current: | 2.3mA @DC24V (LED on) |
Terminal Resistance: | 47KQ |
Output Contact Capacity: | DC24V/1A, 100ms (resistive load) |
Dimensions: | 86mm (length) x 80mm (width) x 33mm (height) (including base, see Figure 2A) |
Weight: | Approximately 82g |
Software Version: | A |
Implementation Standards: | GB16806-2006 |