Relay Module (SFL-INT80)

Relay Module (SFL-INT80)
+
  • Relay Module (SFL-INT80)

Product Consulting

Product Overview

The SFL-INT80 input module is used for intelligent two-wire systems and can set the module address via the handheld address programmer CP900M. It allows for connection with controllers and monitoring of traditional two-wire detectors. In this way, the module can feedback the operational status (normal, open circuit, or alarm) of the monitored detectors to the controller. All monitored two-wire detectors must be compatible with this module. There is an LED indicator controlled by the controller on this module.

 

Technical Specifications

Operating Temperature Range: -10℃~55℃
Operating Humidity Range: 5%~95% RH relative humidity, no condensation
Voltage Range: 15~32 VDC
Static Current: 310μA @ 24VDC without communication
Maximum LED Current: 1.6mA (LED on)
Terminal Resistance: 3.9K ohms
Maximum Monitoring Loop Resistance: 25 ohms
Dimensions: 86mm long x 90mm wide x 30mm high (including base, see Figure 2A)
Weight: Approximately 100g
Software Version: A
Power supply requirements for the monitoring loop - terminals 11, 12
DC Voltage: 24 VDC power limit
Ripple Voltage: Maximum 0.1V RMS
Current: 90mA/module
Certification Mark:

Key words:

Point-type photoelectric smoke fire detector

Point-type temperature sensing fire detector

Fire alarm with sound and light

Manual fire alarm button

Fire hydrant button

Module

Standalone photoelectric smoke fire detector

Others

Related Products


Product Consulting


If you have any questions, you can leave us a message. We have professionals to reply to you. Please fill in the correct contact information!

Submit Message
%{tishi_zhanwei}%
%{tishi_zhanwei}%